Energy Unlimited by Victron

Type

Discharge current

Rated capacity and related discharge time

Discharge time

Discharge current

Effective capacity 1.83 V / cell (11 V)

Discharge time

A (rated)

hours

A (C / 5)

Ah

%

hours

Start

5

100 Ah / 20 h

20

Spiral-cell

2.8

56 Ah / 20 h

20

11.2

52

93

4.6

Semi-traction

10

200 Ah / 20 h

20

40

150

75

3.75

VRLA AGM battery Traction (tubular-plate)

11.5

230 Ah / 20 h

20

46

198

86

4.3

200

1000 Ah / 5 h

5

200

1000

100

5

VRLA-gel Sonnenschein Dryfit A200 VRLA-gel Sonnenschein Dryfit A600

10

200 Ah / 20 h

20

40

158

79

4

150

1500 Ah / 10 h

10

300

900

60

3

Type

Discharge current

Effective capacity 1.83 V / cell (11 V)

Discharge time

Discharge current

Effective capacity 1.75 V / cell (10.5 V)

Discharge time

A (C / 2)

Ah

%

Minutes

A (C / 1)

Ah

%

Minutes

Start

Spiral-cell

28

43

77

92

56

42

75

45

Semi-traction

100

110

55

66

200

90

45

27

VRLA AGM battery Traction (tubular-plate)

115

157

68

82

230

142

62

37

500

700

70

80

1000

400

40

24

VRLA-gel Sonnenschein Dryfit A200 VRLA-gel Sonnenschein Dryfit A600

100

120

60

72

200

100

50

30

750

375

25

15

1500

0*

0

0*

* With a discharge current of 1500 A (C / 1) the voltage of an A600 battery drops almost immediately to 1.65 V / cell (i.e. 9.9 V and 19.8 V for a 12 V respectively 24 V system).

Discharge current is often expressed as a proportion of the rated capacity. For example for a 200 Ah battery C / 5 means a discharge current of 40 A (= 200 Ah / 5).

2.5.4. Capacity and temperature

The effective capacity of a battery varies in reverse proportion to temperature:

- 10°C

10°C 92 %

15°C 95 %

20°C

25°C

30°C

80 %

100 %

103 % 105 %

16

© Victron Energy

Powered by