This interactive publication describes the most compact Energy and Power Hub off-grid up to 1.2mWh Storage and 500kW power.
Technical Specifications
215kWh LiFe Battery Specifications
Battery Module Type Cell Capacity Battery Voltage Range Nominal Current System Storage Power
High Voltage with BDU 280Ah 672~864V 140A (0.5C) 215kWh
AC Specifications (on-grid) Up to 12 in Parallel
Nominal Power AC Nominal Voltage Wiring Nominal Frequency AC Maximum Current Max.number of BESS in parallel Nominal Power AC Nominal Voltage Wiring Nominal Frequency AC Maximum Current Unbalanced Load Capacity On-grid Switching to Off-grid Time Off-grid Switching to On-grid Time Max.number of BESS in parallel
100kW 400V 3P4L+PE
50Hz 158A 12
AC Specifications (off-grid) Up to 5 in Parallel
100kW 400V 3P4L+PE
50Hz 158A 100%
< 20ms < 20ms 5 Max.number of BESS in parallel
Up to 150kW Photovoltaic Input
200-670V Up to three Single channel 50kW
MPPT Voltage Range MPPT channels Input Power Dimensions(W*D*H) Weight Air Conditioner Power Operation Temperature Operation Humidity Protection Level Anti-corrosion Level Noise Level Altitude Cooling System Display Firefighting EMS Communication Certification
System Specifications
1850*1200*2250mm ≈3300 kg 3kW (Cooling capacity) -20~50°C 0~95%(Non-condensing) IP55 C3 ≤75d B ≤3000 m Fan Cooling Touch screen (optional) Aerosol/Heptafluoropropane (FM-200)/Perfluoro (Option)
Ethernet CE/CQC
Selected Pages from Manual
Safiery MEGAFLEX ENERGY HUB 215kWh 100kW
MEGAFLEX ENERGY HUB 215kWh 100kW Product System Overview This product can provide industrial and commercial users with a complete solution of outdoor integrated PV& energy storage system. The product can realize the management, storage and utilization of electric energy through battery storage technology, which can help balance the energy fluctuation between supply and demand and improve the efficiency of energy utilization. Its main function is to distribute photovoltaic DC power or grid AC power to the storage battery and inverter output. This enables users to benefit from services such as peak shaving & load shifting, capacity & demand reduction, new energy upgrading and consumption, demand response and backup power, etc. It can be widely used in scenarios such as charging stations, factories, industrial parks, and commercial buildings. This product can realize integrated delivery, intelligent operation and maintenance management and all-round security assurance.
This product is a combination of high-voltage DC and three-phase AC system, the system are modularized design and the capacity can be flexibly configured. The systematic safety design ensures the efficient and long-life operation of the battery. The product can achieve an integrated on-grid and off-grid solution (switching time between on-grid and of-grid is less than 20 ms) . The system has a storage capacity of 215 kWh.
System schematic topology diagram
1
Copyright. Copying is not allowed unless approved in writing
Page
Safiery MEGAFLEX ENERGY HUB 215kWh 100kW
Component Size: The MEGAFLEX ENERGY HUB is approximately 1846mm long, 1203mm wide (not counting the retainer) and 2250mm high (not counting the lifting ring), the MEGAFLEX ENERGY HUB dimensions are as follows:
MEGAFLEX ENERGY HUB Dimensional drawing *The above pictures are for reference guide only, exact dimensions may vary slightly. The internal structure and composition of the MEGAFLEX ENERGY HUB is shown as below:
4
1
5
2
6
3
7 8
9 10
3
Copyright. Copying is not allowed unless approved in writing
Page
Safiery MEGAFLEX ENERGY HUB 215kWh 100kW
System Internal Modules
1 No.
Battery Module Name
For electrical energy storage Regulates the battery operating temperature Functionality
2
Air conditioner
Collect battery information and control battery charging and discharging
3
BMS module
MPPT module (optional)
4 5
PCS module
AC and DC bi-directional conversion
Automatic fast switching between grid and off-grid can be realized
6
STS module (optional)
Energy management and total control of the entire system
7
EMS Module
PV disconnect switch (optional)
8 9
Grid Switch
Breaks and protects the Grid side
10
Load switch (optional) Breaks and protects the Load side
4
Copyright. Copying is not allowed unless approved in writing
Page
Safiery MEGAFLEX ENERGY HUB 215kWh 100kW
The MEGAFLEX ENERGY HUB secondary electrical switches and external Ethernet ports are as follows:
1 6 Figure 3-6 MEGAFLEX ENERGY HUB secondary switch 2 3 4 5
Table 3-7
Ethernet Port Function Terminal
NO, 1
Name QF1
Functionality Auxiliary master switch Air conditioning switch
2 3 4 5 6 7
QF2 QF3 QF4 QF5
Fan switch UPS switch
BDU socket switch Three-phase meter
METER
LAN1
Ethernet port
5
Copyright. Copying is not allowed unless approved in writing
Page
Safiery MEGAFLEX ENERGY HUB 215kWh 100kW
MEGAFLEX ENERGY HUB Parameter Sheet
Battery system specification parameters: (Applicable to all models)
Battery type
lithium iron phosphate (LiFePO4)
Battery capacity
280Ah
Single module battery configuration
1P16S
Number of packs
One cluster/15 modules
Battery voltage range
672~864V
Rated current
140A ( 0.5C )
Maximum current
150A
System storage capacity
215kWh
AC specification parameters (on-grid): (Applicable to all models)
Rated power
100kW
Rated AC voltage
400V
Wiring method
3P4L+PE
Frequency
50Hz
Maximum AC current
151A
Max number of MEGAFLEX ENERGY HUB 12 Units in Parallel AC specification parameters (off-grid): Rated power
100kW
Rated AC voltage Wiring method
400V
3P4L+PE
Frequency
50Hz 151A 100%
Maximum AC current
Unbalanced load carrying capacity On-grid to off-grid switching time Off-grid to on-grid switching time
< 20ms < 20ms
Maximum number of MEGAFLEX ENERGY HUB units be paralleled 5
6
Copyright. Copying is not allowed unless approved in writing
Page
Safiery MEGAFLEX ENERGY HUB 215kWh 100kW
5
Input voltage
200-670V
Number of MPPT paths
0~3
MPPT Power
50kW per channel
System specification parameters: (Applicable to all models)
Dimension (W*D*H)
1.85*1.2*2.25m
Approx. 3300kg 3kW (cooling capacity) -20~50°C ( derating when above 40 ℃ ) 0~95% ( non-condensing )
Air conditioner power
Working environment temperature Working environment humidity
Protection level
IP55
Anti-corrosion grade
C3
Noise
≤75dB
≤3000m ( Above 2000m need to reduce the amount )
Elevation
Cooling method
Air cooling
Demonstrate
Touch screen (optional)
Optional: Aerosol/heptafluoropropane (FM- 200)/perfluorohexanone (Novec1230)
Fire-fighting
EMS external communications
Ethernet 、 4G CE 、 CQC
Certification
7
Copyright. Copying is not allowed unless approved in writing
Page
Page 1 Page 2 Page 3 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9Powered by FlippingBook