Revert Volts: <FLOATING NUMBER (0.0  16.5)> While in FLOAT mode, if battery voltage drops below ‘RevertVolts’ we assume this indicates a large load has been placed on the system and the regulator will re- start a charge cycle, looping back to BULK mode. Setting ‘RevertVolts’ = 0 will disable this feature.

Revert SOC: <WHOLE NUMBER (0  100)> While in FLOAT mode, if the batteries SOC (State Of Charge) as reported by a CAN attached BMS or other RBM drops below ‘RevertSOC’ the regulator will re-start a charge cycle, looping back to BULK mode. Setting ‘RevertSOC’ = 0 will disable this feature.

In determining to exit Float Mode, a rolling average value for measured Amps and Volts is used. This way short term events (e.g., a surge of a refrigerator starting up and before the Alternator can respond) will not pull the regulator out of Float mode. Note also that the revert Amp – hours are a negative value, and measure the number of AHs removed from the battery after entering Float mode.