$SCA: will reply with “AOK;” if the command was processed successfully. However, to assure the changes are STORED and used the regulator must be reset using the $RBT: command after all changes have been made.

Example - Large alternator powered by large main engine:

 If not already done, set regulator ’ s name  Disable Idle adaptive pullback (alternator has massive cooling capability, and engine has sufficient reserve)  Adjust amp shunt to 250A/75mV  Define engine idle @ 550 RPMs  Must have Alternator Temperature sensor present, else cause regulator to FAULT  Leave other values as default (See Appendix D: )

$SCN:0,MainsAlt,5555@ $SCA:0,95,1.0,0.75,0.50,0,0,0,3333,0,550,60,129@ $RBT:@

Example - Detailed configuration. Large alternator powered by large main engine, 1500AH industrial FLA battery:

Set name to MainsAlt

 Acceptance @ 14.4v until acceptance current is less than 1% of capacity, 8hr max. o 8hr Time limit is set as fall-back in case of battery current sensing failure .  13.2v float - revert back if 2% of capacity is removed  15.3v Equalize, 3Hr duration.  No overcharge nor post-float phases.  Allow Alternator to operate up to 105c  30mV temp comp

$SCN:0,MainsAlt,4449@ $SCA:0,105,1.0,0.75,0.50,0,0,0,3333,0,550,30,0@ $CPA:7 14.4,480,5,0@ $CPO:7 0,0,0,0@ $CPF:7 13.2,-1,0,0,-10,12.7,0@ $CPP:7 0,0,0,0.0@ $CPE:7 15.3,0,180,0@ $CPB:7 0.030,0,-45,45,0,-99,-99,0,0@ $SCO:7,3,1,0,0@ $RBT:@

Example: Shorted warm-up delay to 15 seconds, leaving the rest of the configuration at the default values: $SCA:0,90,1.0,0.75,0.50,-1,0,0, 10000,0,0,15,0@