Safiery CANbus Alternator Controller

ForceTM:

<0, or 1> Setting the value to 1 will enable Tach-mode. (0 = DEFAULT)

Trigger Half-Power Mode RPM: <WHOLE NUMBER ( 0  10,000 )> If the measured engine RPMs is below this value, the regulator will be forced into Half Power mode (See $SCA command above) – in the same way as if the ATS sensor lines are shorted. This feature is most usable of the regulator is CAN connected to the engines J1939 bus and therefore able to reliably pick up engine RPMs (as opposed to using Stator sensing directly).

Set = 0 (DEFAULT) to prevent RPM triggered Half- Power Mode.

Example: $SCT: 12,2.83,0,0,500@

$SCT: will reply with “AOK;” if the command was processed successfully. However, to assure the changes are STORED and used the regulator must be reset using the $RBT: command after all changes have been made.

$SCT: will not be recognized if system has been locked-out via the $SCO: command.