Safiery CANbus Alternator Controller

DST; -- DC-DC ENERGY TRANSFER STATUS “D ST;, DCDC_State, Volts, ,SecondBatVolts, SecondBatCurrent, PrimBatCurrent, DCDC_Temp ”

DCDC_State:

Operational status of optional DC-DC converter. See AltState table above for additional details.

Value 0

- Converter Off (or not present) - Converter in Standby mode

1,4 2,3

- FAULTED (See Fault Code below) 10..40 - Charge Assist Modes: (Reference AST Table above) 71 - 2 nd Battery augment mode.

Volts:

Presently active target Voltage goal/trigger. (See $CDD on page 60 for details)

SecondBatVolts: Measured Secondary battery voltage as reported by the DC-DC converter. Note this may be remotely senses battery voltage, or it may simply be the voltage at the DC DC Converts Secondary Battery terminals.

SecondBatCurrent: If DC-DC Converter is capable, this is the measured current of the secondary battery.

PrimBatCurrent: If DC-DC Converter is capable, this is the measured current of the primary battery.

Note: In both the Primary and Secondary battery current, the values reflect current supplied/consumed by the DC-DC Converter only, not the entire battery. A Positive value indicated energy transfer out of the DC-DC Converter and INTO the respective battery

DCDC_Temp: Internal temperature of the DC_DC Converter, in degrees C

Note: DST: will only be sent if the optional DC-DC converter has been configured and enabled (See $CDD: command on page 60 ). If enabled, it will alternated with the AST status string.